Manufactured up to 5000 A
Panels are manufactured in our own factory, built to each project's drawings and specification.
- Main, sub-main, motor control, ATS, power factor correction and control panels
- Routine checks before delivery: wiring and connections, busbar tightening, insulation measurement and operation test
- Technical support after delivery and installation

Six panel types, built to the project
MDB: Main distribution board
The first distribution point after the incoming supply. It receives power from the transformer or generator and feeds sub-distribution boards and large loads.
Typical contents: An incomer air circuit breaker, main copper busbars, metering and outgoing feeder breakers. Built to the project specification, up to 5000 A.
SMDB: Sub-main distribution board
Receives power from the main distribution board and distributes it within a specific area, floor or group of loads.
Typical contents: An incoming switch or breaker, busbars and outgoing feeder breakers. Sits between the main board and the final distribution boards.
MCC: Motor control center
Groups the starting, protection and control equipment of electric motors in one assembly, for loads such as pumps, fans and conveyors.
Typical contents: An incomer section and motor feeder compartments carrying starters, protection and control devices. Local and remote control as the project requires.
ATS: Automatic transfer switch panel
Transfers the load automatically between two sources, for example the utility supply and a standby generator, and back when the normal source returns.
Typical contents: Transfer switching equipment with electrical and mechanical interlocking, and its control circuit.
PFC: Power factor correction panel
Reduces the reactive power drawn from the network by switching capacitor steps to follow the load, improving the installation power factor.
Typical contents: Capacitor bank steps, a reactive power controller, and step switching and protection devices.
Control: Control panels
House the control, automation and indication equipment of a process or machine, built to the sequence and logic of the project.
Typical contents: Relays, timers, programmable controllers and operator devices, as the project requires.



Key facts
| Parameter | I-Busway panels |
|---|---|
| Rated current | Up to 5000 A |
| Voltage level | Low voltage |
| Components | Selected per project specification |
| Busbars (as photographed) | Copper busbars with colour-coded phases (red, yellow, blue) |
| Enclosure (as photographed) | Free-standing modular cubicles with perforated mounting rails and hinged doors |
| Compartments (as photographed) | Drawer-type feeder compartments and air circuit breaker incomer sections |
| Ratings per project | Short-circuit rating, form of separation and enclosure protection degree are defined in each project specification |


Before delivery
01 Wiring and connections
Every conductor is checked as connected as intended before the panel is energized.
02 Busbar tightening
Busbar and connection bolts are tightened. A loose joint overheats under load, so tightness is confirmed before delivery.
03 Insulation
Insulation is measured between live parts and to earth after assembly.
04 Operation
Switching and control functions are operated to confirm the panel works as designed.
What we need for an offer
A panel offer can be priced only when the project defines its electrical and installation requirements. The list follows the items that IEC 61439-2 (Annex AA) names as subject to agreement between manufacturer and user.
| Information required | Why it is needed |
|---|---|
| System voltage, frequency, earthing | Defines the ratings of the assembly and its devices. |
| Rated current of assembly, incomers, feeders | Defines breakers, busbar size and cubicle size (up to 5000 A). |
| Prospective short-circuit current | Defines the breaking capacity of devices and the short-circuit withstand required. |
| Form of internal separation | Defines the compartment layout and access for maintenance. |
| Enclosure protection (IP) and location | Defines the enclosure and the ambient conditions. |
| Cable or busway entry and space | Defines the cubicle layout and the connection details. |
| Protection settings and discrimination | Defines device types and settings. Discrimination is confirmed from manufacturer data for the devices selected. |
| Metering, indication and control | Defines the devices fitted on each incomer and feeder. |
| Single-line diagram, layouts and BOQ | Basis for the technical review and the financial offer. |
Send your single-line diagram, layout drawings and bill of quantities. Our engineers will review them and prepare a technical and financial offer.
Request a quotationSelected panel projects
| Project | Location | Scope |
|---|---|---|
| Dubai Mall | New Administrative Capital | MCC panels manufactured for this project |
| Residential buildings | Smouha area | Electrical panels for residential buildings |
| Chalets and villas | North Coast | Electrical panels |
| Ministry of Interior, Command and Control building | Busway feeder panels |